STP-200/300/400 Series Instruction Manual
4 Installation of the STP Control Unit
4.1 Name and Function of Each Part
4.1.1 Front Panel
(See Figure 4.1.)
(1) "POWER ON/OFF" Switch (illuminated alternate push button switch,
green LED)
Press this switch to power ON/OFF the STP pump (valid in
MANUAL operation only).
The POWER ON/OFF built-in lamp lights when the power is ON.
(2) "MOTOR START" Switch (momentary push button switch, black)
Press this switch with power ON to start and accelerate the STP
pump (valid in MANUAL operation only).
The "ACCELERATION" lamp lights simultaneously.
(3) "MOTOR STOP" Switch (momentary push button switch, red)
Press this switch to decelerate and stop the STP pump (valid in
MANUAL operation only).
The "NORMAL OPERATION" lamp or the "ACCELERATION"
lamp goes out.
(4) "NORMAL OPERATION" Lamp (green LED)
Lights during rated operation (NORMAL OPERATION state).
(5) "ACCELERATION" Lamp (green LED)
Lights during acceleration (ACCELERATION state).
(6) "OVER TEMPERATURE" Lamp (red LED)
Lights when any of the following abnormalities occurs:
a) When the motor or electromagnet overheats (90 °C or more).
b) When the STP connection cable is not connected.
(7) "BATTERY OPERATION" Lamp (red LED)
Lights while the power is being supplied from the battery to the
STP pump during a power failure.
4-1