Fieldbus ECO-Coupler 750-343 • 99
LED Signaling
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.10.4 Node Status
The I/O-LED indicates the node operation and signals faults occurring.
I/O Meaning
green Data cycle on the internal bus
off No data cycle on the internal bus
red Coupler hardware defective
red
blinks
When starting: internal bus is initialized
During operation: general internal bus fault
red
blinks cyclically
Fault message during internal bus reset and internal fault:
orange Firmware loader active
The Coupler starts after switching on the supply voltage. The I/O-LED flashes
red. Following a fault free start up the I/O-LED changes to a green steady
light.
In the case of a fault, the I/O-LED continues blinking red. The fault is
cyclically displayed with the blink code.
Fig. 3-11: Signaling the node status g012111e
After fixing a fault, restart the Coupler by switching off and on the supply
voltage.