84 • Fieldbus ECO-Coupler 750-343
Configuration of I/O Modules
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.8.3.2 PWM Module
Module Identification
hex
Identification
dec
750-511 0xF2 242
Process Image Input Image
in [byte]
Output Image
in [byte]
Internal bus 6 6
PROFIBUS DP 6 6
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted*) - supplied by the I/O module or
supplied to the I/O module
not plug fitted - set to zero by the Coupler or
ignored by the Coupler
Substitute value channel x
0x0000
*)
... 0x7FFF
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
Coupler configuration, this data is transmitted to
the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
76543210
00Plug 00000
1
76543210
10ID5 ID4 ID3 ID2 ID1 ID0
2
15 14 13 12 11 9 8 7
reserved
3
76543210
00000000
4
15 14 13 12 11 9 8 7
SubVal_Ch1_HB
5
76543210
SubVal_Ch1_LB
6
15 14 13 12 11 10 9 8
SubVal_Ch2_HB
7
76543210
SubVal_Ch2_LB
Plug
5
0
1
Module is physically not present
Module is physically present (default)
SubVal_Ch1 0x0000
:
0xFFFF
Substitute value channel 1
SubVal_Ch2 0x0000
:
0xFFFF
Substitute value channel 2
ID5 .. ID0 Order number less 450 (e.g. 750-511 would be coded as (511-450) = 61
Italic Cannot be changed