Fieldbus ECO-Coupler 750-343 65
Configuring the Coupler
WAGO-I/O-SYSTEM 750
PROFIBUS
The complete parameter record encompasses 34 configuration bytes. The first
10 bytes are laid down by the DP and DPV1 standard. The others contain
manufacturer specific parameters.
Byte No. Bit No. Value Meaning
Standard Parameters
0 0-7 Stations status (see EN 50170)
1 0-7 2-255 Watchdog factor 1
2 0-7 2-255 Watchdog factor 2
Watchdog:
The reaction monitoring is determined in accordance with the
Watchdog_Factor_1 x Watchdog_Factor_2 x 10 ms (1 ms)
3 0-7 11-255 Min T
SDR
,
Earliest time in T
Bit
after which the slave may answer
4 0-7 183, 0xB7 Manufacturer code (high byte)
5 0-7 84, 0x54 Manufacturer code (low byte)
6 0-7 Group allocation,
Broad and multicast telegrams (SYNC, FREEZE)
7 0-7 DPV1 status 1 (see EN 50170)
8 0-7 DPV1 status 2 (see EN 50170)
9 0-7 DPV1 status 3 (see EN 50170)
Manufacturer Parameters
10 0-7 0 Table 0, register 0 LB, reserved
11 0-7 0 Table 0, register 0 HB, reserved
12 0-7 0 Table 0, register 1 LB, reserved
13 0-7 0 Table 0, register 1 HB, reserved
14 Table 0, register 2 LB
0 0 Module diagnostics locked
01
*)
Module diagnostics released
1 0 Internal bus restart after fault: POWER-ON-RESET
11
*)
Internal bus restart after fault: AUTORESET
2-7 0 reserved
15 0-7 0 Table 0, register 2 HB, reserved
16 Table 0, register 3 LB
0-2 '011' reserved
3 0 Data format byte orientated I/O modules: INTEL
31
*)
Data format byte orientated I/O modules: MOTOROLA
4-7 '1100' reserved
17 Table 0, register 3 HB
0-2 Reaction to fieldbus fault:
'000'
'001'
'010'
'011'
*)
'100' - '111'
- Internal bus transmission stopped
- Set output image to zero
- Freeze output image
- Write substitute values
- not possible
3-5 Reaction to internal bus fault:
'000'
*)
'001'
'010'
'011' - '111'
- Leave data exchange
- Set input image to zero
- Freeze input image
- not possible
6-7 '00' reserved
18 0-7 '1100.0011' Table 0, register 4 LB, reserved
19 0-7 '0111.1111' Table 0, register 4 HB, reserved
20 0-7 '0000.0000' Table 100, register 0 LB, reserved
21 0-7 '0000.0001' Table 100, register 0 HB, reserved
22 0-7 '0000.0000' Table 100, register 1 LB, reserved
23 0-7 '0000.0000' Table 100, register 1 HB, reserved
24 0-7 '0000.0000' Table 100, register 2 LB, reserved
25 0-7 '0000.0000' Table 100, register 2 HB, reserved