46 Fieldbus ECO-Coupler 750-343
Hardware
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.2.5 Node Address
The node address (decimal) is determined using two rotary switches on the
electronic module.
Fig. 3-5: Setting the node address gxxxx08x
The binary significance of the individual DIP switches increases according to
the switch number, i.e. the module ID 1 is set by DIP1 = ON, the module ID 8
by DIP4 = ON, etc.
The binary value (2
0
–2
7
) of the dip switches increases from switch 1 to switch
8, a logic 1 being represented by “ON“.
Address DIP8 DIP7 DIP6 DIP5 DIP4 DIP3 DIP2 DIP1
0 - OFF OFF OFF OFF OFF OFF OFF
1
*)
- OFF OFF OFF OFF OFF OFF ON
2 - OFF OFF OFF OFF OFF ON OFF
:
127 - ONONONONONONON
*)
default setting
Node addresses between 0 and 127 can be set.
If an invalid address is set, the coupler adopts the address that has been
assigned via Set_Slave_Address. This address is stored in the power fail safe
EEPROM. The default address is 126.
The node address is saved in the Fieldbus Coupler after switching on the
device (initialization phase). Adjustments of the switch have no effect during
operation.