76 • Fieldbus ECO-Coupler 750-343
Configuration of I/O Modules
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.8.1.10 2 DI/DO I/O Module with 1 Bit Diagnostics per Channel
Module Identification
hex
Identification
dec
750-418 0x30 48
*750-418 0x00 0
Process Image Input Image
in [bit]
Output Image
in [bit]
Internal bus 4 4
PROFIBUS DP 2 2
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted
*)
- supplied to the I/O module
not plug fitted - ignored by the Coupler
Diagnostics channel x The diagnostics information of the
corresponding channel is
released
*)
- transmitted to PROFIBUS DP master
locked - not transmitted to PROFIBUS DP master
*)
Default settings
Parameter
Offset
Information
0
76543210
00Plug 0 Diag
En1
Diag
En0
01
1
76543210
00000111
2
76543210
00000000
Plug
5
0
1
Module is physically not present
Module is physically present (default)
DiagEn0
2
0
1
Diagnostics idle run, overload, short circuit on channel 1
locked
released
DiagEn1
3
0
1
Diagnostics idle run, overload, short circuit on channel 2
locked
released
Italic Cannot be changed