Fieldbus ECO-Coupler 750-343 101
LED Signaling
WAGO-I/O-SYSTEM 750
PROFIBUS
Fault Argument Fault Description Remedy
Fault code 4: Internal Bus Data Fault
0 Data fault on internal bus or
Internal bus interruption on
Coupler
Replace the Coupler
n* (n>0) Internal bus interrupted after I/O
module n
Switch off the supply voltage of the
coupler. Replace the nth module and
switch the supply voltage on again.
Fault code 5: Register Communication Fault
n* Internal bus fault during register
communication with the I/O
module n
Switch off the supply voltage of the
coupler. Replace the nth module and
switch the supply voltage on again.
* The number of blink pulses (n) indicates the position of the I/O module. I/O modules
without data are not counted (e.g. supply module without diagnostics)
Example: the 13
th
I/O Module is Removed.
1. The I/O-LED generates a fault display with the first blink sequence (approx. 10 Hz).
2. The first pause is followed by the second blink sequence (approx. 1 Hz). The I/O-LED
blinks four times and thus signals the fault code 4 (internal bus data fault).
3. The third blink sequence follows the second pause. The I/O-LED blinks twelve times.
The fault argument 12 means that the internal bus is interrupted after the 12
th
I/O
module.