90 • Fieldbus ECO-Coupler 750-343
Diagnostics
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.9.2 PROFIBUS DP Master Address
The PROFIBUS DP master address is located in byte 3 of the slave
diagnostics and includes the address of the master which has been configured
at the node and which has read and write access.
3.1.9.3 Manufacturer‘s Identification
The manufacturer’s identification is located in byte 4 and 5 and includes a 16
bit code, which serves for the identification of the device or the device class.
3.1.9.4 Identification Based Diagnostics
The identification based diagnostics is comprised of a bit field, which contains
one bit of information for each connected module. The individual bit provides
evidence about the current operating status. A 0 means no fault, a 1 indicates a
faulty module condition. The Coupler can be equipped with up to 63 modules,
so that the identification based diagnostics including the header covers 9 bytes
from byte 6 to byte 14.
Byte Information Meaning
6
01001001Header byte
(9 byte identification based diagnostics
incl. header)
7
76543210
8
15 14 13 12 11 10 9 8
9
23 22 21 20 19 18 17 16 Diagnostics allocation to
10
31 30 29 28 27 26 25 24 I/O module n (n=1 ... 63)
11
39 38 37 36 35 34 33 32 Coupler (n=0)
12
47 46 45 44 43 42 41 40
13
55 54 53 52 51 50 49 48
14
63 62 61 60 59 58 57 56