Fieldbus ECO-Coupler 750-343 • 75
Configuration of I/O Modules
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.8.1.9 8 DO I/O Modules
Module
Identification
hex
Identification
dec
750-530 0x20 32
Process Image Input Image
in [bit]
Output Image
in [bit]
Internal bus 0 8
PROFIBUS DP 0 8
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted
*)
- supplied by the I/O module
not plug fitted - ignored by the Coupler
Substitute channel x
0
*)
1
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
Coupler configuration, this data is transmitted to
the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
76543210
00Plug 00011
1
76543210
00000010
2
76543210
SV7 SV6 SV5 SV4 SV3 SV2 SV1 SV0
Plug
5
0
1
Module is physically not present
Module is physically present (default)
SV0
0
Substitute value for channel 1
SV1
1
Substitute value for channel 2
SV2
2
Substitute value for channel 3
SV3
3
Substitute value for channel 4
SV4
4
Substitute value for channel 5
SV5
5
Substitute value for channel 6
SV6
6
Substitute value for channel 7
SV7
7
Substitute value for channel 8
Italic Cannot be changed