Fieldbus ECO-Coupler 750-343 • 93
Diagnostics
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.9.6 Channel Based Diagnostics
The channel based diagnostics is intended for detailing the identification based
diagnostics. A structure is added to the device status for each faulty slot
comprised of a header byte, a byte, the channel type supplying the channel
number and a third byte, which describes the fault type and the channel
organization.
Byte Information Meaning
22
1 0 x x x x x x Header channel based diagnostics
(x: 1 to 63, slots of the module)
23
aaxxxxxxChannel type (a) and
channel number x: 0 to 3
01 Input channel
1 0 Output channel
1 1 Input / output channel
24
t t t xxxxxChannel type (t) and
fault type (x)
0 0 0 No allocation
001 1 Bit
010 2 Bit
011 4 Bit
100 1 Byte
101 1 Word
110 2 Words
25-27
Next channel based diagnostics message (as byte 22 – 24)
28-30
Next channel based diagnostics message (as byte 22 – 24)
...
...
61-63
Last displayable channel based diagnostics message (such as byte 22 – 24)