102 • Fieldbus ECO-Coupler 750-343
Fault Behavior
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.11 Fault Behavior
3.1.11.1 Fieldbus Failure
A fieldbus failure has occurred when the master is switched off or the bus
cable is interrupted. A fault in the master can also lead to a fieldbus failure.
The red BF-LED lights up.
The failure of the fieldbus can activate the substitute value of the I/O modules.
During configuring of the inputs and outputs a substitute value can be laid
down for each channel.
Substitute Value
Strategy
Value (bit orientated)
Digital Output Modules
Value (byte orientated)
Analog Output Modules
Minimum value 0 0 or 4 mA, 0 V
Maximum value 1 20 mA, 10 V
Substitute value 0 or 1 0/4 ... 20 mA, -10 ... +10 V
Stop internal bus Behavior determined by I/O module
The value is entered in the output process image by the Coupler. With I/O
modules with byte orientated data width, e.g. the pulse width module, the
substitute value is determined via the value area.
As soon as the fieldbus is active the process data is transmitted and the output
correspondingly set in the nodes.
3.1.11.2 Internal Bus Fault
An internal bus fault is created, for example, if an I/O module is removed. If
this fault occurs during operation the output modules behave in the same
manner as an I/O module stops.
The I/O-LED blinks red. The slave generates a detailed fault message.
Once the internal bus fault has been fixed the Coupler starts up automatically
in accordance with the configured restart routine. The process data transfer is
then restarted and the outputs reset in the nodes.