Fieldbus ECO-Coupler 750-343 51
Process Image
WAGO-I/O-SYSTEM 750
PROFIBUS
3.1.4.3 Process Images of the I/O-Modules with PROFIBUS-DP
The input and output data of the digital modules are mapped to the Profibus bit
by bit. The configuration of the node determines whether each module
occupies a byte or the data of several modules is grouped in one byte.
The input and output data of the analog modules (D0...Dn) are mapped via
bytes.
In addition to data bytes, specialty modules (counter modules, pulse width
output module, etc.) also send Status Bytes (S) to the Master or receive
Control Bytes (C) from the Master.
Depending on the configuration of the coupler, the status, control and data
bytes of the byte-oriented modules are sent in the Motorola or in the Intel
format.
Note
For the number of input and output bits or bytes of the individual I/O
modules please refer to the corresponding I/O module description.
3.1.4.3.1 2 DI I/O-Modules
750-400, 750-401, 750-405, 750-406, 750- 410, 750-411,750-412
Process Image [bit]
Input Output
PROFIBUS-DP 2 0
3.1.4.3.2 2 DI I/O-Modules with Diagnostics
750-419, 750-425 (1 bit diagnostics / channel)
Process Image [bit]
Input Output
PROFIBUS-DP 2 0
750-418 (1 bit diagnostics / channel, 1 bit acknowledge / channel)
Process Image [bit]
Input Output
PROFIBUS-DP 2 2