The WAGO-I/O-SYSTEM 750 25
Power Supply
WAGO-I/O-SYSTEM 750
PROFIBUS
2.6.2.2 Alignment
Recommendation
A stable network supply cannot be taken for granted always and everywhere.
Therefore, regulated power supply units should be used in order to guarantee
the quality of the supply voltage.
The supply capacity of the ECO coupler or the internal system supply module
(750-613) can be taken from the technical data of the components.
Internal current consumption
*)
Current consumption via system voltage:
5 V for electronics of the bus modules and ECO
coupler
Residual current for
bus terminals
*)
Available current for the bus modules. Provided by
the bus power supply unit. See ECO coupler and
internal system supply module (750-613)
*) cf. catalogue W3 Volume 3, manuals or Internet
Example ECO coupler:
internal current consumption: 350 mA at 5V
residual current for
bus modules: 650 mA at 5V
sum I
(5V) total
: 1000 mA at 5V
The internal current consumption is indicated in the technical data for each bus
terminal. In order to determine the overall requirement, add together the
values of all bus modules in the node.
Attention
If the sum of the internal current consumption exceeds the residual current for
bus modules, then an internal system supply module (750-613) must be
placed before the module where the permissible residual current was
exceeded.
Example:
A node with a PROFIBUS ECO Coupler consists of 20 relay modules
(750-517) and 20 digital input modules (750-405).
Current consumption:
20*105 mA = 2100 mA
10* 2 mA = 20 mA
Sum 2120 mA
The coupler can provide 650 for the bus modules. Consequently, an
internal system supply module (750-613), e.g. in the middle of the
node, should be added.
Recommendation
With the WAGO ProServe® Software smartDESIGNER, the assembly of a
fieldbus node can be configured. The configuration can be tested via the
integrated accuracy check.