88 • Programmable Field Bus Controller 750-833
Configuration and Parameterization of the Modules
WAGO-I/O-SYSTEM 750
Bus System
3.8 Configuration and Parameterization of the Modules
3.8.1 Process Data Channel of the Bus Controller
The process data channel , which has been parameterized as PFC interface and
which requires 2-byte I/O data, is used for communication between WAGO-
I/O-PRO and the run-time system of the field bus controller as described
before. The register interface that has been implicitly allocated for the
identification "750-833 4-byte process data channel “ and that must be
explicitly activated for "750-833 2-byte process data channel “is not usable by
the user and should not be used. If none of these interfaces are used, the
process data channel can be projected with a length of zero.
(750-833 No process data channel).
Module Identification
hex
Identification
dec
750-833 no process data channel 0x00 0
750-833 2 byte process data channel 0xB1 177
750-833 4 byte process data channel 0xB3 179
*)
Default setting
Process Image Input Image
in [Byte]
Output Image
in [Byte]
Internal bus 0 0
PROFIBUS DP 0
*)
/ 2 / 4 0
*)
/ 2 / 4
PFC (CPU) 0 0
*)
Default settings
Parameter Value Meaning
Process data interface The process data interface is for
PFC interface
*)
- program transfer
Register interface - register communication
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
1 0 0 0 0 0 0 0
1
7 6 5 4 3 2 1 0
0 0 1 0 0 0 0 1
2
7 6 5 4 3 2 1 0
0 0 0 0 0 0 Reg
Intf
PFC
Intf
PFCIntf
0
0
1
PFC interface switched off
PFC interface switched on (default)
RegIntf
1
0
1
Register interface switched off (default)
Register interface switched on