Sharp DP-750 Manual de Serviço Página 107

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 240
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 106
Programmable Field Bus Controller 750-833 107
Acyclic Communication According to DP/V1
WAGO-I/O-SYSTEM 750
Bus System
Octet 3
Error_Class Meaning Error_Code_1 Meaning
0 - 9 Reserved
0 Error while reading
1 Error while writing
2 Module error
3 ... 7 Reserved
8 Version conflict
9 Feature not supported
10 Application errors
10 ... 15 Application specific
0 Invalid index
1 Incorrect length while writing
2 Invalid slot
3 Type conflict
4 Invalid area
5 Status conflict
6 Access denied
7 Invalid scaling
8 Invalid parameter
9 Invalid type
11 Access errors
10 ... 15 Application specific
0 Read conflict
1 Write conflict
2 Resource busy
3 Resource not available
4 ... 7 Reserved
12 Resource errors
8 ... 15 Application specific
13 ... 15 Reserved
Vista de página 106
1 2 ... 102 103 104 105 106 107 108 109 110 111 112 ... 239 240

Comentários a estes Manuais

Sem comentários