Programmable Field Bus Controller 750-833 • 87
Parameterization of the Controllers
WAGO-I/O-SYSTEM 750
Bus System
Byte No. Bit No. Value Meaning
Table 0, register 3 HB
0-2
'000'
'001'
'010'
'011'
*)
'100'
'101' - '111'
Reaction to field bus fault:
- stop internal bus transmission
- set output image to zero
- freeze output image
- write substitute values
- PFC fault strategy
- not possible
3-5
'000'
*)
'001'
'010'
'011' - '111'
Reaction to internal bus fault:
- Exit data exchange
- Set input image to zero
- Freeze input image
- not possible
17
6-7 '00' reserved
18 0-7 '1100.0011' Table 0, register 4 LB, reserved
19 0-7 '0111.1111' Table 0, register 4 HB, reserved
20
0
1
2-7
0
1
0
1
'0000 00'
Table 100, Register 0 LB, reserved
PFC mapping binary I/O modules
- process and diagnostics data
- only process data
Configuration of virtual PFC modules
- not possible
- possible
reserved
Table 100, register 0 HB, reserved
0-3 '0001' reserved
4
0
1
Start-up via DPV1-Kanal
- locked
- released
5
0
1
Slot allocation
- DPV1 compatible
- S7 compatible
21
6-7 '00' reserved
22 0-7 '0000.0000' Table 100, register 1 LB, reserved
23 0-7 '0000.0000' Table 100, register 1 HB, reserved
24 0-7 '0000.0000' Table 100, register 2 LB, reserved
25 0-7 '0000.0000' Table 100, register 2 HB, reserved