Programmable Field Bus Controller 750-833 • 105
Acyclic Communication According to DP/V1
WAGO-I/O-SYSTEM 750
Bus System
3.10.2 Complex I/O Modules, Slots 1 ... 63
Index Meaning
'xx00.0000' Table register 0
... ...
'xx11.1010' Table register 58
'xx11.1011' All table registers
'xx11.1100' Diagnostics data of the channel
'xx11.1101' Input data of the channel
'xx11.1110' Output data of the channel
'00xx.xxxx' Table 0 / channel 1
'01xx.xxxx' Table 1 / channel 2
'10xx.xxxx' Table 2 / channel 3
'11xx.xxxx' Table 3 / channel 4
3.10.2.1 Binary I/O Modules, Slots 1 ... 63
T
h
e
e
r
r
o
r
m
Message ”invalid index“ is returned when accessing data areas not available
from the module.
Examples:
Accessing indices of a module that is not physically connected.
Accessing the data areas of the third channel while using a 2-channel
module.
Requesting the input data of an output module.
Requesting the output data of an input module.
Requesting the diagnostics data of a module that has no diagnostics
information.
Index Meaning
'xxx0.0000' Channel 1
... ...
'xxx0.1111' Channel 16
'000x.xxxx' Diagnostics of the channel
'001x.xxxx' Input information of the channel
'010x.xxxx' Output information of the channel
'101x.xxxx'
'1010.0000'
Input information of the module
'110x.xxxx'
'1100.0000'
Output information of the module