162 • I/O Modules
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.1.1 2 DI I/O Modules
Module
Identification
hex
Identification
dec
750-400, 750-401, 750-405, 750-406, 750-410,
750-411, 750-412, 750-413, 750-416, 750-427,
750-435, 750-438, 750-4dd 2 DI
0x10 16
*750-400, *750-401, *750-405, *750-406, *750-410,
*750-411, *750-412, *750-413, *750-416, *750-427,
*750-435, *750-438, *750-4dd 2 DI
0x00 0
Process Image Input Image
in [Bit]
Output Image
in [Bit]
Internal bus 2 0
PROFIBUS DP 2 0
PFC (CPU) 2 0
Parameter Value Meaning
I/O module is physically The I/O module process data is
plug fitted
*)
- supplied by the I/O module
not plug fitted - set to zero by the coupler
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug 0 0 0 0 0
1
7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 1
2
7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0
PFC
6
0
1
Module is mapped into the field bus PA and PFC-PA
Module is exclusively mapped into the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
Italic cannot be changed