I/O Modules • 205
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug 0 0 Diag
En0
0 0
1
7 6 5 4 3 2 1 0
1 1 ID5 ID4 ID3 ID2 ID1 ID0
2
7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0
3
7 6 5 4 3 2 1 0
0 0 0 0 1 1 1 0
Block length in Byte
4
15 14 13 12 11 10 9 8
0 0 0 0 0 1 0 1
Block module PROFIsafe
5
7 6 5 4 3 2 1 0
F_Slot
PROFIsafe module slot
6
7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0
Specifier
7
7 6 5 4 3 2 1 0
0 0
F_CRC_Len
F_SIL
F_Chk
_iPar
F_Chk
SeqNo
F_Prm_Flag1
8
7 6 5 4 3 2 1 0
F_Par_Ver F_Block_ID 0 0 0
F_Prm_Flag2
9
15 14 13 12 11 10 9 8
F_Src_Addr_High
10
7 6 5 4 3 2 1 0
F_Src_Addr_Low
F_Source_Address (1...65534)
11
7 6 5 4 3 2 1 0
F_Dst_Addr_High
12
7 6 5 4 3 2 1 0
F_Dst_Addr_Low
F_Destination_Address (1...65534)
13
15 14 13 12 11 10 9 8
F_WD_Time_High
14
7 6 5 4 3 2 1 0
F_WD_Time_Low
F_Watchdog_Time in ms (1…65535)
15
7 6 5 4 3 2 1 0
F_CRC_High
16
7 6 5 4 3 2 1 0
F_CRC_Low
F_Parameter_CRC (CRC1)
PFC
6
0
1
Module is mapped in the field bus and PFC-PA
Module is exclusively mapped in the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
DiagEn0
2
0
1
Diagnostics locked (default)
Diagnostics released
ID5 .. ID0 Order number less 630 (e. g. 750-650 would be coded as (650-630) = 20)
F_Slot 2..63
PROFIsafe module slot
F_ChkSeqNo 0
1
The consecutive number is not considered in the CRC2 calculation
The consecutive number is considered in the CRC2 calculation
F_Chk_iPar 0 no i-Parameter
F_SIL 0..3
0
1
2
3
SIL class
SIL1
SIL2
SIL3
none
F_CRC_Len 1 2 Byte CRC because of a user data length of less than 12 Byte
F_Block_ID 0 F-Host/F-Slave-Communication-Connection
F_Par_Ver
7..6
0
Valid for PROFIsafe-Profil versions 1.00 – 1.99
F_Src_Addr 1..65534
PROFIsafe-Address of the F-Host
F_Dst_Addr 1..65534
PROFIsafe-Address of the F-Slave
F_WD_Time 150..10000
PROFIsafe-Watchdogtime in ms
F_CRC any
PROFIsafe-CRC
Italic Cannot be changed