Vista de página 200
I/O Modules 201
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.8 DALI/DSI Master
Module
Register Communication
possible
Identification
hex
Identification
dec
Yes 0xB5 181
750-641
No (not possible) - -
Process Image
Input Image
in [Byte]
Output Image
in [Byte]
Internal bus 6 6
Register communication
possible
Yes 6 6
PROFIBUS DP
No (not possible) - -
PFC (CPU) 6 6
Parameter Value Meaning
I/O module is physically The I/O module process data is
plug fitted
*)
- supplied by the I/O module or
supplied to the I/O module
not plug fitted - set to zero by the coupler or
ignored by the coupler
Diagnostics channel x The diagnostics information of the correspond-
ing channel is
released - transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug 0 0 Diag
En0
0 0
1
7 6 5 4 3 2 1 0
1 1 ID5 ID4 ID3 ID2 ID1 ID0
2
15 14 13 12 11 10 9 8
reserved
3
7 6 5 4 3 2 1 0
reserved
PFC
6
0
1
Module is mapped in the field bus and PFC-PA
Module is exclusively mapped in the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
DiagEn0
2
0
1
Diagnostics locked (default)
Diagnostics released
ID5 .. ID0 Order number less 630 (e. g. 750-650 would be coded as (650-630) = 20)