148 • I/O Modules
Design of the Process Data for PROFIBUS-DP
WAGO-I/O-SYSTEM 750
Bus System
5.2.25 Data Exchange Module
750-654
Process Image Length in [Byte]
Register communication possible Input Output
Yes 6 6
No 4 4
Mapping with Register Communication
Data format MOTOROLA INTEL
I/O area Input Output Input Output
S0 C0 S0 C0
D0 D0 D1 D1
D1 D1 D0 D0
D2 D2 D2 D2
D3 D3 D4 D4
Channel 1
D4 D4 D3 D3
Mapping without Register Communication
Data format MOTOROLA INTEL
I/O area Input Output Input Output
D0 D0 D1 D1
D1 D1 D0 D0
D3 D3 D4 D4
Channel 1
D4 D4 D3 D3