I/O Modules 181
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.1.14 2 DI/DO I/O Modules with 1 Bit Diagnostics per Channel
Module
Identification
hex
Identification
dec
750-418 0x30 48
*750-418 0x00 0
Process Image Input Image
in [Bit]
Output Image
in [Bit]
Internal bus 4 4
Diagnostics in the input process image
Yes 4 2
PROFIBUS DP
No 2 2
PFC (CPU) 4
1)
(2
2)
) 4
1)
(2
2)
)
Parameter Value Meaning
I/O module is physically The I/O module process data is
plug fitted
*)
- supplied to the I/O module
not plug fitted - ignored by the coupler
Diagnostics is mapped into the
Input-PAB
The diagnostics information of the I/O module
is
(only for *-Modules) released - mapped into the input process image
locked
*)
- not mapped into the input process image
Diagnostics channel x The diagnostics information of the correspond-
ing channel is
released - transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
*)
Default settings
Parameter (up to Firmware 06)
Offset
Information
0
7 6 5 4 3 2 1 0
0 0 Plug 0 Diag
En1
Diag
En0
0 1
1
7 6 5 4 3 2 1 0
0 0 0 0 0 1 1 1
2
7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0
Parameter (from Firmware 07)
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug
PA-
Diag
0 Diag
En0
0
0 1
1
7 6 5 4 3 2 1 0
0 0 0 1 0 1 1 1
2
7 6 5 4 3 2 1 0
0 0 0 0 0 Diag
En1
0 Diag
En0