I/O Modules 185
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.2 Analog I/O Modules
All analog I/O modules have 2 bytes of extendable parameterization
information, which serves for the identification on the internal bus and the
structure of the mapping table. With analog inputs 2 bytes follow which are
reserved for future options. Modules with diagnostics capability allow the
diagnostics message to be suppressed or released channel for channel.
Analog outputs contain 2 bytes of parameterization data per channel. In this
case the substitute values are saved for the respective channels.
5.4.2.1 2 AI I/O Modules
Module
Register Communication
possible
Identification
hex
Identification
dec
Yes 0xF2 242
750-452, 750-454, 750-456,
750-461, 750-462, 750-465,
750-466, 750-467, 750-469,
750-472, 750-474, 750-475,
750-476, 750-477, 750-478,
750-479, 750-480, 750-483,
750-485, 750-491, 750-492,
750-4aa 2 AI
No 0x51 81
Process Image
Input Image
in [Byte]
Output Image
in [Byte]
Internal bus 6 6
Register communication
Yes 6 6
PROFIBUS DP
No 4 0
PFC (CPU) 4 0
Parameter Value Meaning
I/O module is physically The I/O module process data is:
plug fitted
*)
- supplied by the I/O module
not plug fitted - set to zero by the coupler
Diagnostics channel x The diagnostics information of the correspond-
ing channel is
released - transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug 0 Diag
En1
Diag
En0
0 0
1
7 6 5 4 3 2 1 0
0 1 ID5 ID4 ID3 ID2 ID1 ID0
2
15 14 13 12 11 10 9 8
reserved
3
7 6 5 4 3 2 1 0
reserved