Programmable Field Bus Controller 750-833 111
LED Signaling
WAGO-I/O-SYSTEM 750
Bus System
3.11.3 Fault Message via Blink Code of the BUS LED
Fault Argument Fault Description Remedy
Fault Code 1: Fault in Parameterization Telegram
1 Insufficient parameterization
data
The GSD file is defective or the
parameter data was entered
improperly.
Get in contact with WAGO support.
2 Excessive parameterization data
The GSD file is defective or the
parameter data was entered
improperly.
Get in contact with WAGO support.
Fault Code 2: Fault in Parameterization Telegram
n Faulty parameterized byte n
The n
th
byte is defective.
Get in contact with WAGO support.
Fault Code 3: Fault in Configuration Telegram
1 Insufficient configuration data. Check the configuration because a
terminal was probably forgotten in
the configuration. Load the
configuration and start the coupler
by switching the supply voltage off
and on again.
2 Excessive configuration data. Check the configuration because a
terminal was probably not plugged.
Load the configuration and start the
coupler by switching the supply
voltage off and on again.
Fault Code 4: Fault in Configuration Telegram
n Configuration byte (module) n is
faulty.
Check the n
th
module in the
configuration. Load the
configuration and start the coupler
by switching the supply voltage off
and on again.
Fault Code 5: Faulty Data Length
1 Maximum input data length
exceeded (more than 128 byte
input data).
Switch off the supply voltage of the
coupler. Remove some terminals
from the node and switch the supply
voltage on again.
2 Maximum output data length
exceeded (more than 128 byte
output data).
Switch off the supply voltage of the
coupler. Remove some terminals
from the node and switch the supply
voltage on again.
Fault Code 6: Compilate Buffer Overflow
1 Compilate buffer overflow for
DP process image.
Get in contact with WAGO support.
2 Compilate buffer overflow for
PFC process image.
Get in contact with WAGO support.