I/O Modules 163
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.1.2 2 DI I/O Modules with 1 Bit Diagnostics per Channel
Module
Identification
hex
Identification
dec
750-419, 750-425, 750-4dd 2 DI/DIA
Diagnostics in the input process image
0x30 48
750-419, 750-425, 750-4dd 2 DI/DIA 0x10 16
*750-419, *750-425, *750-4dd 2 DI/DIA 0x00 0
Process Image Input Image
in [Bit]
Output Image
in [Bit]
Internal bus 4 0
Diagnostics in the input process image
Yes 4 0
PROFIBUS DP
No 2 0
PFC (CPU) 4
1)
(2
2)
) 0
Parameter Value Meaning
I/O module is physically The I/O module process data is
plug fitted
*)
- supplied by the I/O module
not plug fitted - set to zero by the coupler
Diagnostics is mapped into the
Input-PAB
The diagnostics information of the I/O module
is
(only for *-Modules) released - mapped into the input process image
locked
*)
- not mapped into the input process image
Diagnostics channel x The diagnostics information of the
corresponding channel is
released - transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
*)
Default settings
Parameter (up to Firmware 06)
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug 0 Diag
En1
Diag
En0
0 1
1
7 6 5 4 3 2 1 0
0 0 0 0 0 1 0 1
2
7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0
Parameter (from Firmware 07)
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug PA-
Diag
0 0 0 1
1
7 6 5 4 3 2 1 0
0 0 0 1 0 1 0 1
2
7 6 5 4 3 2 1 0
0 0 0 0 0 Diag
En1
0 Diag
En0