Sharp JX-9400 Informações Técnicas Página 97

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 211
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 96
upstream end of the duct and its concentration is measured at both ends to give
the flow rate at each.
The leakage of the whole supply or exhaust network may be determined by
measuring the difference between the airflow rate in the main duct (close to the
fan) and the sum of all the flow rates at the individual inlet or extract terminals.
For this purpose, the main airflow rate through the fan may be measured with a
tracer, and the flow rates at the terminals may be determined by one of the
methods described in Chapter 2, ‘Airflow measurements in air han dling
units’, the most appropriate being the compensated flowmeter (see Chapter 2,
‘Compensated flowmeter’).
With this method, the leakage flow rate is the difference of two large
numbers. Therefore, it is not the best one for tight or only slightly leaky
ducts. Because of its ease of use, it can nevertheless be used for diagnosis
purposes, to detect if the ductwork is very le aky or not.
Differential building pressurization
The methods described above measure the leakage of the air duct system. From
the point of view of energy saving, however, it may be useful to measure the air
leakage to or from outside only, and not leakages between the system and the
interior of the building.
For this purpose, the duct system is assumed to be a part of the envelope and
the duct leakage is obtained by difference. In a first test, the closed building is
pressurized after sealing the outdoor air intake and exhaust of the building,
with all the registers and returns open (see Figure 4.10, left). In a second
test, all registers and returns are sealed (see Figure 4.10, right). The difference
in airflow rate between the two tests, for each pressure difference, results from
duct leakage to the outside.
The major advantage of this method is that it needs little equipment, in
addition to that required for envelope leakage measurements. However, it is
prone to inaccuracy since the duct leakage is again obtained as the di fference
between the measurements of two large airflow rates.
Conditioned space
SealSeal
Conditioned space
Seal
Seal
Figure 4.10 Two measurements providing, by difference, the duct leakage
to outside of the conditioned space
76 Ventilation and Airflow in Buildings
Vista de página 96
1 2 ... 92 93 94 95 96 97 98 99 100 101 102 ... 210 211

Comentários a estes Manuais

Sem comentários