The long-term integral method, generally used with passive sources and
samplers, also gives a biased estimate of the average airflow rate. Since the
measurement time is larger, the bias may not be negligible. This technique,
however, provides an unbiased estimate of the average tracer concentration.
If the tracer is used to simulate a contaminant, such experiments are of great
interest for indoor air quality studies.
.
The constant concentration te chnique is accurate and gives an unbiased
estimate of the average airflow rate, but it requires the most technical
equipment.
Table 1.2 Summary of single-zone methods
Suited for
Method name Tracer injection
technique
Interpretation
method
Unbiased
average
Continuous
record
Transient methods (tracer gas concentration changes)
(Simple) decay Decay Identification No No
Two-point decay Decay Integral Yes (Yes)
Step-up Constant rate Identification No No
Steady-state methods (tracer gas concentration is nearly constant)
Pulse Pulse Integral No (Yes)
Constant injection Constant rate Direct solution Yes
No
Long-term integral Any Integral No No
Constant
concentration
Constant
concentration Integral Yes Yes
Note: y Under condition.
Source: Sherman, 1990.
Table 1.3 Summary of multi-zone methods
Tracer injection strategy Unbiased average of
time-varying flow
Well suited for
continuous record
Single tracer (repeated measurements)
Pulse injection No No
Decay No No
Constant injection rate No No
Constant concentration Yes No
Multi-tracer
Pulse injection No No
Decay Yes* No
Constant injection rate No Yes
Constant concentration Yes Yes
Note:
Only for a two-point estimate.
Airflow Rates in Buildings 13