
Air sampling and analysis
Air at the four locations is sampled with a pump through small tubes filled with
an adsorbing medium (for example, activated charcoal, T
ENAX). The sampling
rate is about 0.1 l of air per minute. VOCs accumulate in the compound by
absorption, as long as the medium is not saturated.
The sampling tube is then hermetically sealed and taken to the laboratory
for further analysis. The VOCs are desorbed by heating the tubes and they
are stored in a cold trap. The content of the trap is then injected in the
column of a gas chromatograph. A flame ioni zation detector (FID) is used to
detect and measure the amount of each compound, while a mass spectrograph
is used to help identify the compound (Mogl et al., 1995). An FID analyser can
also be used on site to sample and analyse the air but, if pulse injection is used,
this analysis should be performed at periodical and short intervals at the four
locations shown in Figure 6.10.
Which VOCs?
The ‘natural’ concentration of VOCs is often (and hopefully!) not large enough
to provide accurate measurement of transfer rate. Therefore, a mix of various
VOCs should be injected in the extract duct in order to obtain concentrations
that are significantly larger than concentrations in outdoor air. Criteria to
determine the VOCs’ mixture are:
.
The compounds are selected on their occurrence in buildings. Sources are
paints, paper, solvents, carpets and human emissions.
.
They are representative of the different organic famil ies with the character-
istic of their functional group and sa turation degree. The result is different
boiling point and polarity.
.
They are easy to analyse and the results are significant. The concentrations
chosen must be under the saturation limit of the T
ENAX sampler.
.
The compounds should be easy to manipulate
.
They should not give a long-lasting and bad smell in the room and should
present an acceptable toxicity at the measured concentrations.
Lists of VOCs found most often in office buildings, as well as proposals for
VOC cocktails can be found in the literature (Brow n et al., 1994; Hodgson,
1995; Maroni et al., 1995; Molhave et al., 1997; Wolkoff et al., 1997; van der
Syringe
Hot air blower (200 °C)
Stainless steel
turnings
Ø 6 mm copper tube
Figure 6.11 Flash evaporation device for injecting the VOCs
Source: Roulet et al., 2000.
Contaminants in Air Handling Units 119
Comentários a estes Manuais